OVERVIEW
Although battery resistance testing methods are improving and very popular, battery discharge test still is the most accurate and
discharge testing in their maintenance management.
FEATURES
Wide Range
IDCE-930CT also offers selectable quantity of cells which voltages below the stop point, this design could help you to locate more lag batteries in once constant discharging.
IDCE-930CT can save several independent discharge records automatically without Laptop monitoring, non-volatile internal memory guarantees the data security even in unexpected shutdown.
Intelligent judge program: IDCE-930CT can identify the situations that the battery voltages reach the threshold value or the signal missing by manual mistake. Avoiding manual interruption in the discharging, this revolutionary program makes the test stable and smooth.
IDCE-930CT provides ample protective measures for various abnormal situations during discharge. Automatic termination, LCD prompt and beep warning would assist users to make proper treatments.
Connected with clamp current, IDCE-930CT cooperate other types in IDCE-CT series or any other load units, and clamp current can count external current in.
PC SOFTWARE
SPECIFICATIONS
Discharge Ranges Voltage range Current range 8-40V (12/24/36V) 0-300 A 40-54V (48V) 0-280 A 54-64V (60V) 0-220 A 85-110V (96V) 0-140 A 95-150V(110V) 0-120 A 150-265V(220V) 0-60 A 150-285V(240V) 0-55 A Current measurement Internal current range 0-300 A Accuracy & resolution ±0.5%FS+0.6A, 0.1 A External current range 0-600 A (optional current clamp) Accuracy & resolution ±1%FS+0.3A, 0.1 A Voltage measurement Group voltage range 8-285 V Accuracy & resolution ±0.3%FS+0.3V, 0.1 V Cell voltage range 0-15V Accuracy & resolution ±0.2%FS+0.005V, 0.001 V Power Supply Power supply voltage 110/220 V AC (-20% to +20%) Frequency 50/60 Hz Power consumption 200W(max) Communication & Storage Communicate port USB/RS485 Internal memory 128Mbit Flash CE Certificate LVD standardsEN 61010-1:2010
EN 61010-2-030
EMC standards EN 61326-1:2013EN 61000-3-2:2014EN 61000-3-3:2013 Environment Operation temperature -5 to 35℃ (full power)35 to 50℃ (limited power) Storage temperature -40 to 70℃ Humidity 5% - 90% RH Altitude below 4000 m Working noise <70 dB Dimensions & Weight Main tester 505 x 346 x 296 mm Carrying case 610 x 390 x 535 mm Weight 28 kg (main tester only)52 kg (included all accessoriesand carrying case)0.3 kg (each wireless module) Accessories Carry case 1 x 610 x 390 x 535 mm, 15 kg Power cable 2 x 3 m cables 120 mm² AC power cord 1 x 3 wires x 1 mm² Software 1 x Softcopy in USB disk User manual 1 USB disk 1 x 16GB Current clamp 1 x 200A or 600A (Optional)