Fuzhou Fuguang Electronics Co., Ltd.

IDCE-910CT Battery Discharger & Capacity Tester
IDCE-910CT Battery Discharger & Capacity Tester
Hotline:86-591-83305821
E-mail:global@fuguang.com

OVERVIEW

Although battery resistance testing methods are improving and very popular, battery discharge test still is the most accurate and

reliable method for actual capacity evaluation of battery groups. Because only constant current discharge can perfectly simulate
the working status under loading for batteries, power supply departments in many companies and utilities keep the periodic

discharge testing in their maintenance management.


Because the DC power systems in various industrial utilities are using different voltage level battery groups (24V, 48V, 110V, 120V,
220V, 240V etc.), and most of the professional users hope to find an unattended and automatic instrument to simplify discharge
process, the battery discharge tester with intelligent designs and super voltage variability for almost all battery types would be
preferable.

FEATURES


Wide Range

IDCE-910CT can support 12-240 V battery groups, the application of IDCE-910CT includes:


                                                           

Multiple Adjustable Stop Points
IDCE-910CT offers 4 adjustable points for test stop points to avoid excessive discharge:

IDCE-910CT also offers selectable quantity of cells which voltages below the stop point, this design could help you to locate more lag batteries in once constant discharging.


Selectable Discharge Modes
IDCE-910CT provides 3 discharge modes for different test requirements:


7 inch Touch LCD Display
Super big size touch LCD can display all real time data andgraphs and support the click operations directly, humanized input method and menu designs simplified operating process.


Presetting Function
The presetting function for discharge parametersprovides multiple profiles editing and saving interface forsetting up all discharge parameters in advance, thisdesign can skip the setting procedures for the same discharging, simplify the operation and speed up the test.


Internal Memory
IDCE-910CT can save several independent discharge records automatically without Laptop monitoring, non-volatile internal memory guarantees the data security even in unexpected shutdown.


Wireless modules for cells voltage measuring are available for 1.2V/2V/6V/12V batteries voltage monitoring during discharge test.



Each wireless module can monitor 4 batteries simultaneously. Compared with the traditional cable voltage measuring method that each module only can monitor 1 battery, the new wiring operation is much easier.



With proper number wireless modules, main tester can real time scan and display the voltage data of each battery during the discharging, and display the histogram of all batteries to follow the battery voltage tracks inwhole discharging process.


Intelligent judge program: IDCE-910CT can identify the situations that the battery voltages reach the threshold value or the signal missing by manual mistake. Avoiding manual interruption in the discharging, this revolutionary program makes the test stable and smooth.


IDCE-910CT also supports cable modules for special requirements.


Multiple Protections & Alarms


IDCE-910CT provides ample protective measures for various abnormal situations during discharge. Automatic termination, emergency stop button, LCD prompt and beep warning would assist users to make proper treatments.


Extendable & Compatible
Connected with clamp current, IDCE-910CT cooperate other types in IDCE-CT series or any other load units, and clamp current can count external current in.


PC SOFTWARE

Support data downloading and analyzing through real time communication or USB memory devices


The software interface includes: battery voltages curve and bar chart, battery resistances bar chart, group voltage curve, current curve, capacities histogram, data form and so on.


Powerful capacity estimating function, the software can predict the capacity of each battery in the tested group.


The software shows the data by various ways like bar charts, curve, and form. And users can magnify or minify any windows to read more details. Automatically create EXCEL data report, it’s so convenient to send or download the data.


SPECIFICATIONS

Discharge Ranges
Voltage range
Current range
8-54V (12/24/36/48V)
0-150 A
54-64V (60V)
0-110 A
64-85V (80V)
0-80 A
85-110V (96V)
0-70 A
95-150V(110V)
0-60 A
150-265V(220V)
0-30 A
150-285V(240V)
0-25 A
Current measurement
Internal current range
0-150 A
Accuracy & resolution
±0.5%FS+0.6A, 0.1 A
External current range
0-600 A (optional current clamp)
Accuracy & resolution
±1%FS+0.3A, 0.1 A
Voltage measurement
Group voltage range
8-285 V
Accuracy & resolution
Accuracy & resolution
Cell voltage range
0-15V
Accuracy & resolution
±0.2%FS+0.005V, 0.001 V
Power Supply
Power supply voltage
110/220 V AC (-20% to +20%)
Frequency
50/60 Hz
Power consumption
150W(max)
Communication & Storage
Communicate port
USB/RS485
Internal memory
128Mbit Flash
CE Certificate
LVD standards

EN 61010-1:2010

EN 61010-2-030:2010

EMC standards
EN 61326-1:2013
EN 61000-3-2:2014
EN 61000-3-3:2013
Environment
Operation temperature
-5 to 35℃ (full power)
35 to 50℃ (limited power)
Storage temperature
-40 to 70℃
Humidity
5% - 90% RH
Altitude
below 4000 m
Working noise
<70 dB
Dimensions & Weight
Main tester
505 x 296 x 266 mm
Carrying case
610 x 390 x 455 mm
Weight
17 kg (main tester only)
32 kg (included all accessories
and carrying case)
0.3 kg (each wireless module)
Accessories
Carry case
1 x 610 x 390 x 455 mm, 10 kg
Power cable
2 x 3 m cables 50 mm²
AC power cord
1 x 3 wires x 1 mm²
Software
1 x Softcopy in USB disk
User manual
1
USB disk
1 x 16GB
Current clamp
1 x 200A or 600A (Optional)



Message
Name:*
Tel:
E-mail:*
Company:
Msg:*

COPYRIGHT © 1993-2024 Fuzhou Fuguang Electronics Co., Ltd. ALL RIGHTS RESERVED

Home
Products
Tel