OVERVIEW
Although battery resistance testing methods are improving and very popular, battery discharge test still is the most accurate and reliable method for actual capacity evaluation of battery groups. Because only constant current discharge can perfectly simulate the working status under loading for batteries, power supply departments in many companies and utilities keep the periodic discharge testing in their maintenance management.
220V DC is very common voltage level for batteries applications in Power utilities & Oil companies. Because the battery groups are playing key roles in standby power supply, the regular discharge test is necessary for improve the stability of the power network. Most of the professional users hope to find an unattended and automatic instrument to simplify discharge process. We believe IDCE-2206S & IDCE-2415S will be your best choice!
FEATURES
Adjustable Current
IDCE-2206S/2415S can provide 0-60A/0-150A (steps: 1A) adjustable current for different test requests. During the test, the current will keep constant.
IDCE-2206S | IDCE-2415S |
Battery Nominal Voltage |
Max Discharge Current |
Battery Nominal Voltage | Max Discharge Current |
48V | 13A | 48V | 33A |
110/120V | 25A | 110/120V | 80A |
220V | 60A | 220/240V | 150A |
Multiple Adjustable Stop Points
IDCE-2206S/2415S offers 3 adjustable points for test stop points to avoid excessive discharge:
IDCE-2206S |
IDCE-2415S |
Stop Point |
Setting Range |
Stop Point |
Setting Range |
Group Low Voltage |
40.0 - 220.0 V |
Group Low Voltage |
40.0 - 220.0 V |
Discharge Time |
0 - 20 Hour |
Discharge Time |
0 - 20 Hour |
Discharge Capacity |
0 - 9999 AH |
Discharge Capacity |
0 - 9999 AH |
Extendable & Compatible
Connecting with clamp current, IDCE-2206S/2415S cooperate other types in IDCE-S series or any other load units, and clamp current can count external current in.
Multiple Protections & Alarms
Malfunctions |
LCD prompt |
Beep warning |
Input over-voltage |
√ |
√ |
Reverse polarity |
√ |
√ |
Overload |
√ |
√ |
Overheat |
√ |
√ |
IDCE-2206S/2415S provides ample protective measures for various abnormal situations during discharge. Automatic termination, LCD prompt and beep warning would assist users to make proper treatments.
SPECIFICATIONS
Discharge Ranges
IDCE-2206S |
IDCE-2415S |
Voltage range |
Current range |
Voltage range | Current range |
40-90V |
0-13 A |
40-90V |
0-33 A |
90-130V |
0-25 A |
90-130V |
0-80 A |
190-265V | 0-60A | 190-285V | 0-150A |
Current measurement
IDCE-2206S | IDCE-2415S |
Internal current range |
0-60 A |
Internal current range |
0-150 A |
Accuracy & resolution |
≤±0.5%FS, 0.1 A |
Accuracy & resolution |
≤±0.5%FS, 0.1 A |
External current range |
0-100 A |
External current range |
0-200 A |
Accuracy & resolution |
≤±1%FS, 0.1 A |
Accuracy & resolution |
≤±1%FS, 0.1 A |
Voltage measurement
IDCE-2206S | IDCE-2415S |
Group voltage range |
40-265 V |
Group voltage range |
40-285 V |
Accuracy & resolution |
≤±0.5%FS, 0.1 V |
Accuracy & resolution |
≤±0.5%FS, 0.1 V |
DC Power Supply
IDCE-2206S | IDCE-2415S |
Power supply voltage |
220 V AC (-20% to +30%) |
Power supply voltage |
220 V AC (-20% to +30%) |
Frequency |
50/60 Hz |
Frequency |
50/60 Hz |
Power consumption |
200W(max) |
Power consumption |
500W(max) |
Environment
IDCE-2206S | IDCE-2415S |
Operation temperature |
-5 to 50°C |
Operation temperature |
-5 to 50°C |
Storage temperature |
-40 to 70°C |
Storage temperature |
-40 to 70°C |
Humidity |
5% - 95% RH |
Humidity |
5% - 95% RH |
Altitude |
below 4000 m |
Altitude |
below 4000 m |
Working noise |
<60 dB |
Working noise |
<60 dB |
Dimensions & Weight
IDCE-2206S | IDCE-2415S |
Main tester |
682 x 224 x 395 mm |
Main tester |
910 x 224 x 629 mm |
Carrying case |
370 x 600 x 800 mm |
Carrying case |
1100 x 900 x 350 mm |
Weight |
20 kg (main tester only) |
Weight |
52 kg (main tester only) |
Accessories
IDCE-2206S
IDCE-2415S
Carry case |
1 x 370 x 600 x 800 mm |
Carry case |
1 x 1100 x 900 x 350 mm |
Power cable |
2 x 3 m cables 16 mm2 |
Power cable |
2 x 3 m cables 50 mm2 |
User manual |
1 |
User manual |
1 |
AC power wire |
1 x 3 wires x 1 mm2 |
AC power wire |
1 x 3 wires x 1 mm2 |